PRODUCTS

Current position: PRODUCTS  /   SWITCHGEARS  /   Fixed low voltage switchgears  /  

Product Classification
Contact us

Tel : +86-577-62665555
       +86-577-62668988

Business Email : Jacky.dxm@qq.com

XGN66-12 Fixed metal closed switch equipment

XGN66-12 Fixed metal closed switch equipment

XGN66-12 Fixed metal closed switch equipment

Overview XGN66-12 Fixed metal closed switch equipment(abbreviated as switch cabinet) is used in 12KV and /below three phase AC. 50Hz,power systems to accept and distribute electrical energy. It meets requirements of the national standards that are G
Published in2018-08-03
2421 Views

Detailed description

Overview

XGN66-12 Fixed metal closed switch equipment (abbreviated as switch cabinet) is used in 12KV and /below three phase AC. 50Hz,power systems to accept and distribute electrical energy. It meets requirements of the national standards that are GB3906 《3-35KV AC. metal closed switchgear》and DLT404 《Indoor AC. high voltage open closet order technical conditions》 of the Ministry of Electrical Industry,and also meets requirements of international standards IEC60298 《3-35KV AC. metal closed switchgear and control equipment under》. The cabinet is welded up with high quality angle steel. Breaker room is located in middle part of the cabinet. It is easy to install, inspect and maintain. The standard equipped  breaker is ZN63A (VS1-12) circuit breaker, and has a pressure release channel to ensure personal safety. Being equipped with advanced and reliable rotary isolation switch, it can be ensured personal safely enter the circuit breaker room at middle place of main busbar for maintenance. For having a complete and fully functional mandatory mechanical locking device,it is simple and effective to meet the "five prevention" requirements. Front door is equipped with an observation window. It can clearly observe working state of functional devices in the cabinet, and operating mechanism has same interlocking functions so that XGN locking mechanism ensures XGN2-12 cabinet to be simply, reliably, conveniently and practically operated.

Application

It is mainly used for power plants, substations,industrial and mining enterprises, high-rise buildings and other places, and can also be used for opening and closing offices with ring network cabinets.

Normal use conditions

1. Altitude is 1000m;  if there are special requirements, it can be noted when ordering.

2. Environment  temperature:-25 C ~+40 C;

3. Relative temperature average value is not more than 95%, and monthly relative temperature average value is not more than 90%.

4. Seismic ability: 8 degrees;

5, No violent vibration and impact and fire,chemical corrosion and explosion hazards.

4. Applied standards:

·IEC298·IEC265 ·IEC129
·IEC694·IEC420 ·EC56
·IEC529·IEC932 ·GB3804
·GB3906·GB11022

Main technical data

No.

Item

Unit

Technical data

1

Rated voltage

kV

3.6, 7.2, 12

2

Rated current

A

630    1000

1250    2000

2500    3150

3

Rated short circuit breaking current

kA

20

31.5

40

4

Rated short time withstand current

kA

20

31.5

40

5

Rated peak withstand current

kA

50

80

100

6

Rated short circuit making current

kA

50

80

100

7

Rated duration of short circuit

s


4


8

Degree of protection


IP2X

9

Bus system


Single bus, single bus with bypass, double bus

10

Operating method


Electromagnetism, spring storage energy

11

Outline dimension

mm


950^1000x2300 (below 1250A)
1000x1000x2300 (over 1250A)

Other Similar Products

  • JXF indoor/JFF outdoor enclosure box

  • TBBX高压无功就地补偿装置

  • XL-12系列低压动力配电柜

  • jp系列综合配电箱

  • JXF明装低压配电箱